IEC 60309

From HwB

Revision as of 17:39, 15 February 2007 by Joakim (Talk | contribs)

Industrial power connectors. Location of earth pin ensures that different types of plug and jack cannot be connected.

Contents

Pinout

Number of pins
2P+E 3P+E 3PN+E
Ground
pin
location
1 - - -
2 >50V, 300-500Hz, green housing >50V, 300-500Hz, green housing >50V, 300-500Hz, green housing
3 50-250V AC 380V, 50 Hz
440V, 60Hz
220/380V, 50Hz
250/440V, 60Hz
4 100-130V AC, yellow housing 100-130V AC, yellow housing 57/100 - 75/130V AC, yellow housing
5 277V, 60Hz 600-690V AC, black housing 347/600 - 400/690V AC, black housing
6 200-250V AC, blue housing 380-415V AC, red housing 200/346 - 240/415V AC, red housing
7 480-500V AC, black housing 480-500V AC, black housing 277/480V - 288/500V AC, black housing
8 250V DC - -
9 380-415V AC, red housing 200-250V AC, blue housing 120/208V - 144/250V AC, blue housing
10 - >50V, 100-300Hz, green housing -
11 - 440-460V, 60Hz, red housing 250/440V - 265/460V, 60Hz, red housing
12 - - -

Standards

  • IEC 60309-2
  • EN 60309-2
  • BS EN60309-2
  • CEE17 (superseded)
  • BS 4343 (superseded)

Contributors